beautypg.com

MPI Technologies FCX User Manual

Page 10

background image

,167$//$7,21

7\SLFDO LQVWDOODWLRQ H[DPSOHV

The flue/combustion air system piping may be either
horizontal or vertical or a combination of both, ob-
serving the following:

• The maximum unrestricted horizontal or verti-

cal flue length shall not be more than 16.4 ft
(5 m).

• For each 90-degree elbow used in the flue sys-

tem, subtract 3.3 ft (1m) from the total allowa-
ble length.

• For each 45-degree elbow used in the flue sys-

tem, subtract 1.65 ft (0.5m) from the total allo-
wable length.

• Horizontal runs of the flue system must pitch

down 3/4 inch per yard (2 cm per m) of length
towards the boiler to facilitate proper flue pro-
ducts condensate drainage.

• Termination of a horizontal flue system shall

not be less than 5.96 ft(1.8m) above ground
unless other provisions are made to minimize
the likelihood of flue/combustion air intake
blockage.

• Do not place the flue terminal less than 3.3 ft.

(1 m) from a ventilation hole or opening in a
building.

• Termination of a vertical flue must provide at

least 12 inches (30cm) above the roof jack to
the combustion air intake collar.

• If there are two units in the installation with ver-

tical flue systems, the termination of the sys-
tems must be separated by 16 inches (40cm).

All flue-piping components must be assembled to
provide an airtight flue/ combustion air system.

Application of liquid soap over the flue pipes to be
joined will aid in assembly of the parts.

Typical installation examples appear in the illustra-
tion that follow.

6WUDLJKW %DODQFHG )OXH &RQILJXUDWLRQ

Option: Straight Horizontal Flue Kit

$QJOHG %DODQFHG )OXH &RQILJXUDWLRQ

Option: Angled Horizontal Flue Kit

40 cm

mini

30 cm

mini

16 In.

- 12 In.

1

,80 m

5.

9 f

t.

1 in

2.8 ft

1,

80

m

5.

9 f

t.

1 in