4
Specifications
*
The values given in the table for the noise level reflect the levels measured at a position 1.5 meters immediately below the unit in an anechoic
chamber.
*
The noise at the air outlets is the values at a 45° angle, 1.5 meters in front of the unit.
*
The above values apply during Lossnay ventilation when the fan speed is set to high speed.
*
The values for 150 and 200 type main unit outlet noise show in the case of 1 supply air duct.
Model
name
Voltage (V)
Line
frequency
(Hz)
Current (A)
Power
consumption
(W)
Static
pressure
Air volume
Noise (dB(A))
Exchange efficiency (%)
Weight
(kg)
Air
outlets
Below
the unit
(m /h)
3
(L/S)
Temperature
Enthalpy
Heating Cooling
1-Phase
220 - 240
LGH-
15RX
4
50
0.29-0.31
63-73
150
42
77
60
70
64.5
17
1-Phase
220 - 240
LGH-
25RX
4
50
0.39-0.40
85-96
250
69
78
50
70
65
21
1-Phase
220 - 240
LGH-
35RX
4
50
0.71-0.71
154-167
350
97
79
70
70
68
30
1-Phase
220 - 240
LGH-
50RX
4
50
0.89-0.90
193-214
500 139
77
60
67.5
64.5
33
1-Phase
220 - 240
LGH-
80RX
4
50
1.60-1.60
340-370
800 222
78
100
71
67
61
1000
1-Phase
220 - 240
LGH-
150RX
4
50
3.10-3.10
670-730
1500 417
79
100
72
68
35.5-36.5
124
1-Phase
220 - 240
LGH-
200RX
4
50
(1mmH
2
O = 9.80665Pa)
4.20-4.20
910-980
2000 556
79
90
71
67
140
6.1
5.1
7.1
6.1
10.2
10.2
1-Phase
220 - 240
LGH-
100RX
4
50
2.00-2.00
440-475
278
79
100
71
67
69
10.2
9.2
(mmH
2
O) (Pa)
60Hz : Invalid in EU
60
0.33-0.35
72-84
150
42
77
70
8.2 80
64.5
17
60
0.45-0.47
98-112
250
69
78
70
6.1 60
65
21
60
0.83-0.87
180-207
350
97
79
70
5.1 50
68
30
60
1.05-1.10
231-262
500 139
77
67.5
6.1 60
64.5
33
60
3.80-3.90
820-935
1500 417
79
72
12.2 120
68
124
30-31.5
33-34
35-37
37.5-39.5
43-44
44-45
45.5-46.5
45-46
31-32.5
33.5-34.5
34-36
36.5-39
43.5-44.5
24-25
25-26
28-30
29.5-31.5
32-33
37-38
34-35
25-26
25.5-26.5
27-29
28.5-31
1-Phase
220 - 240
LGH-
65RX
4
50
1.30-1.30
270-300
650 181
76
50
68
64.5
46
5.1
60
1.50-1.60
320-370
650 181
76
68
7.1 70
64.5
46
40.5-41
40.5-41
32.5-33
32.5-33
60
2.60-2.70
565-635
1000 278
79
71
11.2 110
67
69
45-47
34-36
60
1.90-2.00
405-465
800 222
78
71
12.2 120
67
61
42-43.5
31-32.5
35-36
60
5.30-5.40
1155-1295 2000 556
79
71
10.2 100
67
140
45-47
36.5-38.5
Consult with your dealer about the after-sales services provided for this
Lossnay product.
After-sales servicing
Assembly after maintenance
1. Bearing in mind the following points, assemble the parts following the
sequence for their removal in reverse.
•
Attach the air filters to the magic tape on the Lossnay core(s).
•
Arrange the Lossnay core with the air filter side downward.
2. Press the filter button on the remote controller (PZ-41SLB-E) two
times in succession.
(This clears the Lossnay’s operating time cumulative data.)
Maintenance (Continued)
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer.
Consult with your dealer concerning the cost of inspection or
repair work.
Relevant button
FILTER
(Press twice)
FILTER
Relevant display items