1. For connection of a remote controller (PZ-41SLB-E)

If the Lossnay’s operation is linked with the operation of an external device such as an air conditioner, the method of use will differ, so carry out
the appropriate operation in accordance with the following table. Also, please see the installation and user’s manual for the remote controller
(PZ-41SLB-E).

2. For connection of a Lossnay remote

controller (PZ-52SF-E), Mitsubishi
Electric Air-Conditioner Network
System (MELANS) or City Multi.

This is to be incorporated and used in the Mitsubishi Electric Air-
Conditioner Network System.
This is interlocked with the City Multi and operated by it.
If the Lossnay remote controller (PZ-52SF-E) is used, the Lossnay
may be operated independently if connected to City Multi.
For details, refer to the operating manual of PZ-52SF-E.

Lossnay operation using the Lossnay remote controller (PZ-52SF-
E) should need the power supply unit. Refer to the system diagram
below.

Note

If this is to be used with the Lossnay remote controller (PZ-
52SF-E), refer to the manuals for both the PZ-52SF-E instal-
lation and operating manual.

Remote controller PZ-41SLB-E cannot be used with this sys-
tem.

System diagram

Power supply
unit

Power
supply

MELANS

PAC-SC34KUA

Lossnay unit
LGH-**RX

4

-E

Lossnay remote controller (PZ-52SF-E)

M-NET transmission line

Basic system

LOSSNAY VENTILATE setting

Both fresh air supply and return air pass through the Lossnay core(s).
Resulting in full heat exchange. Lossnay ventilate setting is used for
cooling in the summer and heating in the winter period.

BY-PASS VENTILATE setting

The fresh air passes through the Lossnay core(s) and the return
room air is exhausted direct. Lossnay bypass ventilate is normally
operated during the spring/autumn months.

Example of System

Function

• If 2 remote controllers are used, the last

controller to be used has priority. (Last
Command)

Operation

Run using the remote
controller.

City Multi
indoor unit

Power
supply

A/C’s remote controller

Lossnay unit
LGH-**RX

4

-E

M-NET transmission line

Interlocked to the City Multi indoor unit

Operation

• If you would like to turn ON the Lossnay

alone while the external device is OFF,
operate it by the Lossnay remote control-
ler.

• The fan speed is on “High”.
• The ventilation mode is “Ventilation Mode

Auto Select”.

If an external device is
connected the “On/Off”
function of this device will
also control the Lossnay
operation.

Lossnay

Power Supply

Remote Controller

(Optional parts)

(PZ-41SLB-E)

Lossnay

Power Supply

External device

Remote Controller

(Optional parts)

(PZ-41SLB-E)

Power Supply

Operation switch for the external device

Lossnay

Power Supply

Power Supply

Operation switch for the external device

External device

AUTOMATIC VENTILATION setting

The automatic damper mode automatically provides the correct ven-
tilation for the conditions in the room. The following shows the effect
“By-pass” ventilation will have under various conditions.

Fresh air

Exhaust air

Lossnay core

Damper

Return air

Damper

Return air

Supply air

Supply air

Lossnay core

Exhaust air

Fresh air

Models LGH-15 to 100 RX

4

Models LGH-150 and 200 RX

4

Exhaust air

Fresh air

Lossnay core

Damper

Return air

Supply air

Exhaust air

Fresh air

Lossnay core

Damper

Models LGH-15 to 100 RX

4

Models LGH-150 and 200 RX

4

Fresh air

Exhaust air

Return air
Supply air

Return air
Supply air

Return air
Supply air

Exhaust air

Fresh air