Minuteman UPS MCP 10001 User Manual
Page 9
Page 7
2.3 WIRING DESCRIPTION
The wiring method for the MCP SERIES is shown in Figure A.
Figure A - Wiring Diagram for MCP 6001, & MCP10001
REAR VIEW
Wiring Instructions:
1. Utility panel circuit breaker required is 35A or larger
2. Utility wire guage must be 8 guage or larger.
3. Connect utility per drawing.
4. Connect output load connections and jumper wires for correct voltages per drawings.
5. Use proper size AWG wires for all connections.
6 K V A
O N L Y
1 0 K V A
O N L Y
NOTE: PARA SYSTEMS DOES NOT PROVIDE AC OUTPUT OVERCURRENT PROTEC-
TION. OUTPUT OVERCURRENT PROTECTION IS TO BE PROVIDED BY THE USER.