Minuteman UPS MCP 10001 User Manual
Page 4
Page 2
Power
Rating
Model
No.
Freq.
(Hz)
Input
Output
Voltage
Voltage
Current
Current
6KVA
4.2KW
MCP 6001
50/60
170-276
VAC
50/60
170-276
VAC
120, 120/120, 208,
120/208, 240, 120/240V
120, 120/120, 208,
120/208, 240, 120/240V
10KVA
7KW
MCP10001
56A
50, 25/25, 28.8,
25/28.8, 25, 25/25A
83.3, 41.7/41.7, 48.1,
41.7/48.1, 41.7, 41.7/41.7A
33A
1.3 PRODUCT SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
INPUT
Voltage:
As listed
Phase:
single phase with ground
Frequency:
50/60Hz +/- 5%, auto selection
Power factor:
>/= 0.97
OUTPUT
Output voltage regulation:
+/-3%
Power factor:
0.7 lag to unity
Frequency regulation:
+/-5%, phase lock to input under normal conditions, +/-0.5% of nominal frequency,
under normal operation or battery mode.
Distortion:
+/-3.0% THD at full linear load, +/-7% THD at full non-linear load
Overload Capacity:
>130% +/-10% for 200 ms, 105% for 10 second
Load Crest Ratio
3:1 maximum
OPERATING ENVIRONMENT
Ambient temperature:
10 to 40 degrees Centigrade
Operation humidity:
20% to 90%, non-condensing
Altitude:
less than 1500M above sea level
Storage temperature:
-15 to 40º C
MECHANICAL SPECIFICATIONS
Model Number
Dimensions
H x W x D
Weight
Net (Shipping)
MCP 6001
MCP10001
31.5 x 10.25 x 23.25 in.
80 x 26 x 59 cm
296(311.6)lb.
134.3(141.3)Kg
38 x 13.5 x 26.5 in.
96.5 x 34.3 x 67.3 cm
519.6(552.2)lb.
235.7(250.5)Kg