When using an isolation tranasformer, ensure that the load is balanced.

When using #6 AWG wire 2 in. are required for wire bending space opposite the terminals. 1 1/2 in. for #8 AWG.
3 in. for #3 AWG and #4 AWG. 3 1/2 in. for #2 AWG.

For 6KVA output configuration #1, #2, #3, #4, #5, #6, and #7 use #6 AWG, 75ºC copper wire. For 10KVA
output voltage configuration #1, use #2 AWG,115ºC copper wire. For configurations #2, #3, #4, #5, and #6 use
#6 AWG, 75ºC copper wire.

Tightening torque for pressure wire connectors having screws

Size of wire that is to be used

for connection of the unit

AWG/kcmil

8

6-4

3
2

mm

2

8.4

13.3-21.2

26.7
33.6

Tightening torque, pound-inches (N-m)

Slot width - 0.047 in.
(1.2mm) or less, and
slot length - 1/4 inch

(6.4mm) or less

25 (2.8)
35 (4.0)

35 (4.0)
40 (4.5)

Slot width - over

0.047 in. (1.2mm)

and slot length - 1/4

inch (6.4mm)

25 (2.8)
45 (5.1)
50 (5.6)
50 (5.6)

Hexagonal head - external

drive socket wrench

Split-bolt

connectors

80 (9.0)

165 (18.6)

275 (31.1)
275 (31.1)

Other

connection

s

75 (8.5)

110 (12.4)

150 (16.9)
150 (16.9)

Slotted head No. 10 (4.7mm) and Larger

Page 9

Maximum current

rating (amperes)

60
90

100
150

Maximum size of

equipment grounding or

bonding conductor AWG

10

8
8
6

Minimum size of

grounding electrode

conductor AWG

8
8
6
6

Maximum size of

equipment grounding or

bonding conductor AWG

8
8
6
6

Size of grounding electrode conductors (copper wire)

OUTPUT CONFIGURATION #5 = 240VAC

L1 L2 L3 L4 N G





240VAC

OUTPUT CONFIGURATION #6 = 120VAC / 240VAC

L1 L2 L3 L4 N G


120VAC 120VAC


240VAC