1.4
Prerequisites to Installation
An efficient installation depends on careful planning and site preparation. Installation of the equipment must be han-
dled by skilled technicians and electricians familiar with the special requirements of high-voltage electrical equip-
ment. The installation must comply with the requirements of the National Electrical Code (ANSI/NFPA 70, latest
issue) and local codes as applicable, and safety standard, UL1012 listed; ul1449 compliant; meets FCC Cat. A.
1.5
General Description
The overall function of the Topaz 100 Ultra-Isolator is to attenuate transients and noise that originate on the
incoming power lines and provide a newly derived, isolated power source.
The Topaz 100 Ultra-Isolators are used to protect sensitive electronic equipment and computers from power line
noise and transients. There are common disturbances on the power lines caused by lightning, motor starting and
stopping, utility network switching and general electrical noise, which will adversely affect sensitive electronic
equipment, especially computers.
The Topaz 100 Ultra-Isolator utilizes a unique method of shielding and isolation which provides low capacitive
coupling between input and output circuits. This low capacitance, together with a highly effective filter circuit, results
in ultra high common mode and normal mode noise attenuation.
1.5.1
Electrical Specifications
Input voltage
120, 240, 480VAC – depending on model
Common mode noise attenuation
140dB @ 100KHz
Normal mode noise attenuation
65dB @ 100KHz
Overload capacity
600% for 1 cycle, 300% for 30 seconds
Dielectric strength
2500 VAC minimum
Frequency
60Hz ± 5%
Impedance
3% to 6%, depending on size
Efficiency
93% to 97%, depending on size
Input voltage range
Nominal voltage ± 10%
Load regulation
2% to 5%, no load to full load at unity power factor
Harmonic distortion
Adds less than 1% THD, under linear loading
Coil insulation
200ºC
Temperature Rise
115ºC max rise above a 40ºC ambient
Electro-magnetic interference
Less than 0.2 gauss @ 3 ft.
1.5.2
Environmental Specifications
Audible noise
Less than 50dB measured @ 3ft.
Operating temperature
0 to 40º C
Storage temperature
-20º to +50º C
Operating altitude
5,000 ft. (without derating)
Operating humidity
95% relative (non-condensing)