Maintenance, 1 trouble-shooting – MGE UPS Systems 2200 User Manual
Page 20
Page 20 -
34007115EN/AA
Troubleshooting requiring MGE UPS SYSTEMS after-sales support
4. Maintenance
4.1 Trouble-shooting
Indication
LED 17 goes ON and
the buzzer sounds
continuously.
Signification
UPS electronics have detected a UPS fault.
◗
The connected equipment is no longer supplied.
The equipment connected to the UPS is no
longer protected.
Correction
Call the after-sales support
department.
Indication
LED 18 flashes and the
buzzer beeps once.
LED 17 flashes.
Signification
UPS overload. The power drawn by the connected
equipment exceeds UPS capacity.
A battery fault was detected during the automatic
battery test.
Correction
Check the power drawn by the
equipment and disconnect any non-
priority devices.
Replace the battery module (see
section 4.2).
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (all versions)
Indication
The outlets are not
supplied with power even
though button 15 is ON.
Signification
One of the output-protection circuit breakers 7
on the rear panel is open.
Correction
◗
Make sure there is not a short-
circuit on the outlets.
◗
Clear the overload on the
concerned outlets by balancing the
equipment loads over the outlets.
◗
Close the circuit breaker.
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (3000/3000 XL versions only)