MITSUBISHI ELECTRIC BC CONTROLLER CMB-P-V-F User Manual

Page 3

background image

3

4.1

[Fig. 4.1.1]

4

Outdoor

unit side

(Unit: mm)

Piping portion

High pressure

Low pressure

Item

(liquid) side

(gas) side

PURY-200

ø25.4 (Brazing)

PURY-P200

ø19.05

PURY-250

(Brazing)

ø28.58 (Brazing)

PURY-P250

Indoor unit side

ø9.52 (Flare)

ø15.88 (Flare)

A

To outdoor unit

B

End connection (brazing)

C

BC controller

D

Reducer (accessory)

E

Indoor unit

F

Less than 40

G

Combined piping kit (Model name: CMY-R160-H)

H

Branch pipe (Model name: CMY-Y102S-F)

I

Up to three units for 1 branch hole; total capacity: below 80 (but same in cooling/
heating mode)

*1. For connecting 20 to 40 type indoor units
Connect indoor units using the reducers (specials) supplied with BC controllers.

*2. For connecting 100 to 140 type indoor units (or more than a total indoor

unit capacity of 81)

After combining two branch holes using an optionally available combined piping
kit (CMY-R160-H), connect indoor units.

*3. Connection of plural indoor units with one connection (or joint pipe)

Total capacity of connectable indoor units: Less than 80 (Less than 160 with
joint pipe)

Number of connectable indoor units: Maximum 3 Sets

Branch pipe: Use the branch pipe for CITYMULTI Y Series (CMY-Y102S-F)

Selection of refrigerant piping (Piping size of A/B sections in the above fig-
ure)
Select the size according to the total capacity of indoor units to be installed
downstream.

Total capacity of indoor units

Liquid line

Gas line

Below 80

ш9.52

ш15.88

81 to 160

ш12.7

ш19.05

E

E

E

E

E

I

E

A B

G

*2

H

*1

D

50-63

100-140

*3

C

*4

F

A

BC controller

B

Locally procured pipe ø28.56

C

Locally procured pipe ø25.4

D

Refrigerant conn. pipe (accessory)

For PURY-250

PURY-P250

[Fig. 4.1.2]

For PURY-200

PURY-P200

4.2

[Fig. 4.2.1]

This manual is related to the following products: