Notes: For MS/MSH, MF, MSM

*1. Rating conditions (cooling)

_____

Indoor: 80˚F DB, 67˚F WB Outdoor: 95˚F DB, 75˚F WB

(heating)

_____

Indoor: 70˚F DB, 60˚F WB Outdoor: 47˚F DB, 43˚F WB

*2. Include auxiliary electric heater operations at 115V. (MSH09EW, MSH12EN, MSH15EN)
*3. Rated voltage of compressor and fan motor is 115V. (MUM18EW)
*4. Values are for each indoor unit.
*5. Depth of outdoor unit ( ) includes thickness of fan grille.

Operating Range

Notes: For PK/PKH, PC/PCH, PL/PLH
* 1. Rating conditions (cooling)

_____

Indoor: 80˚F DB, 67˚F WB Outdoor: 95˚F DB, 75˚F WB

(heating)

_____

Indoor: 70˚F DB, 60˚F WB Outdoor: 47˚F DB, 43˚F WB

* 2. Rating conditions (heating)

_____

Indoor: 70˚F DB, 60˚F WB Outdoor: 17˚F DB, 15˚F WB

* 3. Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.

Operating Range

*5 With Wind Baffle installed.

General Specifications

MODEL

MS09EW, MSH09EW, MSM18EW

MF12EN, MF15EN

MSM30EN

(MS09EWX2•MS15ENX1)

MS12EN, MS15EN, MSH12EN, MSH15EN

PK18EK, PKH18EK, PL18FK, PLH18FK,
PK12EK, PL12FK

PK24EK, PKH24EK, PC24EK, PCH24FK,
PL24FK, PK24EK

PK30EK, PKH30EK, PL30FK, PLH30FK,
PC30EK, PCH30EK, PL36FK, PLH36FK,
PC36EK, PCH36EK, PL42FK2, PC42EK

PLH42FK, PCH42EK

MS09EW

MS15EN

Max. Height

Difference (ft)

25

25

25

130

164

Max. Tubing

Length (ft)

49

65

49

130

164

Liquid

1/4

3/8

1/2

Gas

3/8

1/2

3/8

5/8

5/8

3/4

7/8

Connection

Method

Flared

Refrigerant Tubing

Tubing (OD)/N

MODEL

Cooling

Heating

Maximum

Minimum

Maximum

Minimum

Indoor air intake temperature

95˚F DB, 71˚F WB

67˚F DB, 57˚F WB

80˚F DB, 67˚F WB

70˚F DB, 60˚F WB

Outdoor air intake temperature

115˚F DB

*5 0˚F DB

75˚F DB, 65˚F WB

17˚F DB, 15˚F WB

MODEL

Cooling

Heating

Maximum

Minimum

Maximum

Minimum

Indoor air intake temperature

95˚F DB, 71˚F WB

67˚F DB, 57˚F WB

80˚F DB, 67˚F WB

70˚F DB, 60˚F WB

Outdoor air intake temperature

115˚F DB

67˚F DB

75˚F DB, 65˚F WB

17˚F DB, 15˚F WB

REFRIGERANT TUBING SIZE

*For more details refer to

Technical And Service Manual. All specifications are subject to change without notice.

Form No. MIT-MRS-24-97

3100 AVALON RIDGE PL. STE. 200, NORCROSS, GA 30071
CALL: 770-613-5840 OR 800-433-4822 (PRESS 3) FAX: 800-889-9904