beautypg.com

Maytag MDG-75 User Manual

Page 20

background image

16

IMPORTANT: Minimum duct size for a dryer that is vented vertically is 12-inches (30.48 cm) for a

round duct or an equivalent of 120 square inches (774 square centimeters). THE
DUCT SIZE MUST NOT
BE REDUCED ANYWHERE DOWN STREAM
OF THE DRYER.

IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be

increased to an extent. When the ductwork approaches the maximum limits noted in
this manual, a professional heating, venting, and air conditioning (HVAC) firm should
be
consulted for proper venting information.

ALL ductwork should be smooth inside with no projections from sheet metal screws or other obstructions
which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be
connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the building.
Inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and
cleaning of lint from the ductwork.

NOTE: Where the exhaust duct passes through a wall, ceiling, or roof made of combustible materials,

the opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct
must be centered within this opening.

a. Outside Ductwork Protection

1) To protect the outside end of horizontal ductwork from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the ductwork travels vertically up
through the roof, it should be protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening
and the nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust

ductwork.