Manitowoc Ice E-0400 User Manual
Manitowoc Ice Freezers
7623973
LOW PRESSURE CONTROL E-0400 REMOTE
Installation Instructions
1. Turn ice machine off at toggle switch so machine pumps down and shuts off at 2 psig.
2. CAUTION - Disconnect power at circuit breaker after machine has pumped down.
3. Mount low-pressure control using the existing capacitor mounting stud, washer, nut, and extra washer included in kit.
Install extra washer under existing washer (see Illustration, Sheet 2).
4. Use procedure "A" or "B":
A. Recover refrigerant. When work is complete, weigh in new refrigerant.
-OR-
B. Pump down to 2 lb. and close receiver valve.
a. Using pinch-off tool, pinch off 1/4" line to cap tubes (see Illustration, Sheet 2).
NOTE: Pinch-off is required because the refrigerant is isolated from the low side between receiver valve
and hot gas solenoid.
b. Cut top of 1/4" stub off.
c. Route new low-pressure control cap tube around compressor, as shown (Illustration, Sheet 2). Swage
new low-pressure 1/4" stub and solder to existing stub.
d. Open pinch-off.
e. Purge a little refrigerant out of low/suction service valve.
5. Run lead wires from new pressure control into control box. Do not allow wires to touch any refrigerant lines.
6. Remove lead wires from existing low-pressure control and connect to new lead wires using heat shrink sleeve as insulation
over connection (see Illustration, Sheet 3).
7. Remove old low-pressure control.
8. Make sure control is set as follows: left arrow (differential) 25 lb., right arrow (cut-in) 27 lb.
9. Operate ice machine, pull water curtain open, or shut off at toggle switch two to three times to ensure ice machine shuts off
at approximately 2 lb. consistently.
Manitowoc Ice, Inc.
2110 South 26 Street, P.O. Box 1720, Manitowoc, WI 54221-1720 USA 8008653
Telephone 920-682-0161, Fax - Sales: 920-683-7589, Service/Parts: 920-683-7585, Other: 920-683-7879 Sheet 1 of 1
Web Site - www.manitowocice.com Rev. 02/14/01