OPERATION INDICATOR

Not lighted

Blinking

Lighted

OPERATION INDICATOR

Not lighted

Blinking

Lighted

NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first

detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.

No.

1

Symptom

Operation indicator lamp

Detection method

Check point

Abnormal

point

0.5-second ON

0.5-second OFF

When the electricity is not conducted to the
interlock switch (Fan) of the horizontal vane.

• Refer to 9-6.

E

"Check of

installation of the horizontal
vane".

Indoor unit
and outdoor
unit do not
operate.

Attachment
of the
horizontal
vane

All lamps flash at the same time.

No.

Symptom

Operation indicator lamp

Detection method

Check point

Abnormal

point

1

MXZ type
Operation
mode
setting

Outdoor unit
operates but
indoor unit
does not
operate.

When the operation mode of the each indoor
unit is differently set to COOL(includes DRY)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
first has the priority.

• Unify the operation mode.
Refer to service manual
OB377.

2.5-second OFF

Right lamp flash

· Flashing of OPERATION INDICATOR lamp (all lamps) indicates abnormality.

· Flashing of OPERATION INDICATOR lamp (right-hand side lamp) indicates

abnormality.

· OPERATION INDICATOR lamp (left-hand side lamp) is lighted.

NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.

Self check table

9-5. Trouble criterion of main parts

MSZ-GA22VA -

MSZ-GA25VA -

MSZ-GA35VA -

E1

E1

E1

Part name

Figure

Check method and criterion

Indoor fan motor(MF)

Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)

Normal

8 k

"

~ 20 k

"

Abnormal

Open or short-circuit

Room temperature
thermistor(RT11)

Indoor coil thermistor
(RT12(MAIN), RT13(SUB))

Horizontal vane
motor(MV)

Normal

BRN-other one

Abnormal

Open or short-circuit

Measure the resistance between the terminals with a tester.
(Part temperature 10

°

C ~ 30

°

C)

235

"

~ 255

"

Color of the lead wire

Check 9-6.

A

.

RED

YLW
BRN

ORN

GRN

ROTOR

OB378_--1qxp 05.1.17 12:55 Page 16