This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass
circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed.
Recommended Breaker (MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
Recommended
Breaker (Aac)
30 480 36 45
50 480 60 80
80 480 96 125
AC input and AC output over current protection and disconnect devices shall be field
supplied and installed. DC output over current protection and disconnect device shall
be field supplied and installed. The over current protection device shall be rated as
indicated in TABLE 1.4.