MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-2

This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass
circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed.
Recommended Breaker (MCCB)'s Specifications are as follows:

Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)

Recommended

Breaker (Aac)

30 480 36 45

50 480 60 80

80 480 96 125

AC input and AC output over current protection and disconnect devices shall be field
supplied and installed. DC output over current protection and disconnect device shall
be field supplied and installed. The over current protection device shall be rated as
indicated in TABLE 1.4.

WARNING 2