MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual
Page 18
MITSUBISHI ELECTRIC 2033D SERIES UPS
MITSUBISHI
ELECTRIC
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-12
TABLE 1.3 Detail of Specifications
Rated Output kVA
30
50
80
Rated Output kW
24
40
64
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +15% to -15% (-30% can be operated)
Frequency
60 Hz (45.4Hz to 65Hz)
Reflected Current THD
4% typ. at 100% load; 7% typ. at 50% load
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +/-10%
Frequency 60
Hz
BATTERY
Type Lead
Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
401 Vdc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 4 wire
Voltage
120/208 V, 277/480 V
Voltage Stability
+/-1%
Frequency 60
Hz
Frequency Stability
+/-0.05% in free running mode
Power Factor
0.8 nominal
Power Factor range
0.8 - 1.0 lagging (within output kW rating)
Voltage THD
2% typical THD at 100% Linear Load
5% typical THD at 100% non-linear load
Transient Response
+/-3% at 100% load step
+/-1% at loss/return of AC power
+/-3% at load transfer to/from static bypass
Transient Recovery
16.6ms
Inverter Overload
125% for 10 minutes, 150% for 1 minute
System Overload
1000% for 1 cycle
(with bypass available)
Bypass Overload
150% for 1 minutes
ENVIRONMENTAL
Cooling Forced
Air
Operating Temperature
32゚F ~ 104゚F (0゚C - 40゚C)
Recommended 68゚F - 86゚F (20゚C - 30゚C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 ~ 9000 feet No Derating
Location
Indoor (free from corrosive gases and dust)
(PCB conformally coated for use in industrial environment)
Paint Color
Munsell 5Y7/1 (Beige)