beautypg.com

Mitsubishi electric – MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 50

background image

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-3

MITSUBISHI ELECTRIC 2033D SERIES UPS

(Note 9)

Code

indication

Status message

Contents

Guidance

(Note 1)

Buzzer

(Note 2)
External

send-out

contact

(Note 3)

Failure

lamp

UF213

INV. OR CONV.

OVERTEMPERATURE

Overheating of main circuit parts

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF214

COOLING FAN

ABNORMAL

Abnormality of cooling fan inside panel

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF255 52C

ABNORMAL

52C turned OFF during inverter power

supply

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF256

OUTPUT VOLTAGE

ABNORMAL

Inverter output voltage fell out of +/- 5%

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF258 LOAD

ABNORMAL

More than 4 overcurrent transfers in 5

minutes

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF259

ANOTHER UPS

ABNORMAL

Inverter output voltage bus

abnormality

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF301

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF302

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF303

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF305

UPS CONTROL CIRCUIT

ERROR

Control clock abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF306

UPS CONTROL CIRCUIT

ERROR

Control power source circuit

abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF309

INVERTER VOLTAGE

ABNORMAL

Inverter output voltage abnormality

before inverter power supply

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF310

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF349

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF371

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF372

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF373

UPS CONTROL CIRCUIT

ERROR

Control microcomputer abnormality

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF453 52L OPERATION ERROR 52L operated abnormally

CHECK 52L

[2]

Minor

Flicker

UA801

AC INPUT VOLTAGE OUT

OF RANGE

AC input voltage deviates from +17%

to –32% range

CHECK INPUT

POWER

SOURCE

[2] Alarm -

UA803

INPUT PHASE

ROTATION ERROR

Input phase abnormal

CHECK INPUT

POWER

SOURCE

[2] Alarm -