PAGE 42 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)

Shutdown Procedure

To shutdown the generator use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 39 to the OFF position.

3. Let the engine cool by running it for 3-5 minutes with no

load applied.

4. Place the

MPEC Control Switch (Figure 55) to the

OFF/RESET position.

Figure 55. MPEC Control Switch (Off/Reset)

5. Verify that the

all status LED on the MPEC display

are OFF (not lit).

6. Remove all loads from the generator.

DCA-125USJ (50 HZ)— GENERATOR SHUT-DOWN PROCEDURE

NEVER stop the engine suddenly except
in an emergency. DO NOT use the

emergency stop switch a as method of
shutting down the generator. This switch is

ONLY to be used in the event of an
emergency.

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION:

Emergency Shutdown Procedure

1. To shut-down the engine in the event of an emergency,

switch the

MAIN, GFCI and LOAD (Figure 39) circuit

breakers to OFF position.

2. Place the

MPEC Control Switch switch (Figure 55) to

the OFF/RESET position.