If electrolyte contacts the skin, wash it off immediately with water. If electrolyte

contacts the eyes, flush thoroughly and immediately with water. Seek medical

attention.

·

Determine if the battery is inadvertently grounded. If inadvertently grounded, remove

source of ground. Contact with any part of a grounded battery can result in electric

shock. The likelihood of such shock will be reduced if such grounds are removed

during installation and maintenance.

·

Do not lay tools or metal parts on top of batteries.

·

Discharge static electricity from body before touching batteries by first touching a

grounded metal surface.

·

Disconnect charging source prior to connecting or disconnecting battery terminals.

·

Ensure all connections to the new batteries are EXACTLY the same as they were

from the old batteries.

·

Verify all of the battery brackets and mechanical fittings are replaced exactly as they

were removed.

·

Spilled electrolyte should be washed down with a suitable acid neutralizing agent.

Use approximately 1 pound of bicarbonate soda to approximately one gallon of

water. The solution should be added until reaction has ceased. The resulting liquid

should be flushed with water.

CAUTION!

These batteries are recyclable. The batteries contain lead

and pose a hazard to the environment and human health if not disposed of
properly. Refer to local codes for proper disposal requirements or return
the batteries to MINUTEMAN.

Battery pack connection:

Ex. MCP 3000 connected to 2-MCPBP3’s

External Battery Packs

UPS