4. pipe forming and drain piping – MITSUBISHI ELECTRIC MSZ-FD09/12NA User Manual

Page 5

background image

2-4-2. DRAIN PIPING

• If the extension drain hose has to pass through a room, be sure to wrap it with insu-

ODWLRQ¿HOGVXSSOLHG

• The drain hose should point downward for easy drain. (Fig. 1)
‡ ,I WKH GUDLQ KRVH SURYLGHG ZLWK WKH LQGRRU XQLW LV WRR VKRUW FRQQHFW LW ZLWK D ¿HOG

supplied drain hose (I). (Fig. 2)

• When connecting the drain hose to a hard vinyl chloride pipe, be sure to insert it se-

curely into the pipe. (Fig. 3)

Do not make drain piping as shown below.

Do not raise

Accumulated
drain water

Air

Waving

Water
leakage

Water
leakage

Water
leakage

Tip of drain
hose dipped
in water

Ditch

At least
1-31/32 in.
(50 mm)
gap

Downward
slope

Drain
hose

Soft hose I.D.
19/32 in.
(15 mm)

Drain hose

Hard vinyl chloride pipe
I.D. 1-3/16 in.
(30 mm)

Insert
securely

Different
diameter joint

27-9/16 in.
(70 cm)

or more

Fig. 1

Fig. 2

Fig. 3

Liquid pipe

Gas pipe

Felt tape (7)

Indoor/outdoor unit
connecting wire (A)

Piping tape (G)

2-4. PIPE FORMING AND DRAIN PIPING

2-4-1. PIPE FORMING

• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not crowded or bent.
• Do not pull the hose when applying the tape.
• When the drain hose passes the room, be sure to wrap it with insulation material

¿HOGVXSSOLHG

Note:
Make sure not to damage the cover of refrigerant pipe when attaching it back on with
screws.

Left or left-rear piping
Note:
Be sure to reattach the drain hose and the drain cap if the piping is being installed on
left or bottom left of unit, otherwise, water could drip down from the drain hose.

3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\IHOWWDSH

from the end.

Felt tape (7) overlap width should be 1/3 the tape width. Use a bandage stopper at

the end of felt tape (7).

2) Pull out the drain cap at the back right of the indoor unit. (Fig. 1)

• Hold the convex section at the end and pull the drain cap.

3) Pull out the drain hose at the back left of the indoor unit. (Fig. 2)

• Hold the claw marked by the arrows and pull out the drain hose forward.

4) Put the drain cap into the section to which the drain hose is to be attached at the rear

of the indoor unit. (Fig. 3)
• Insert a screwdriver into the hole on the cap and insert the cap fully into the drain

pan.

5) Insert the drain hose fully into the drain pan at the back right of the indoor unit. (Fig. 4)

• Check if the hose is hooked securely to the projection of its inserting part at the

drain pan.

6) Insert the drain hose into wall hole sleeve (C), and attach the upper part of indoor

unit onto the installation plate (1). Then, shift the indoor unit completely to the left to
make placing the piping in the back of the unit easier.

7) Cut out a piece of cardboard from the shipping box, roll it up, hook it onto the back

rib, and use it as a spacer to lift the indoor unit. (Fig. 5)

8) Connect the refrigerant piping with the extension pipe (B).
9) Attach the lower part of the indoor unit into the installation plate (1).

Remove panel for piping
on left side of unit.

Drain cap

Drain hose

Drain cap

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Piping tape (G)

Felt tape (7)

Rear or bottom piping
3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\SLSLQJWDSH

(G) from the end.

2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the up-

per part of the indoor unit on the installation plate (1).

3) Check if the indoor unit is attached securely on the installation plate (1) by moving

the unit to left and right.

4) Attach the lower part of the indoor unit into the installation plate (1).

Right piping
Note:
Before performing the following, make sure that wiring is completed, and the conduit
cover is installed. (Refer to 2-3.)
1) Place the refrigerant piping and the drain hose together, shift them to left side of the

XQLWDQGWKHQ¿UPO\DSSO\SLSLQJWDSH*IURPWKHHQG

2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the up-

per part of the indoor unit on the installation plate (1).

3) Check if the indoor unit is attached securely on the installation plate (1) by moving

the unit to left and right.

4) Attach the lower part of the indoor unit into the installation plate (1).

To the left

Remove panel
for piping on
right side of
unit

Remove panel for piping on
bottom side of unit