Moxa Technologies 5600 User Manual
Page 36

NPort 5600 Series User’s Manual
Web Console Configuration
Port alias
Setting
Factory Default
Necessity
1 to 15 characters
(E.g., PLC-No.1)
None Optional
“Port Alias” is specially designed to allow easy identification of the serial devices which are
connected to NPort’s serial port.
Serial Parameters
Check the serial communication parameters in your Serial Device’s user’s manual. You should
set up NPort’s serial parameters with the same communication parameters used by your serial
devices.
Baud rate
Setting
Factory Default
Necessity
50 bps to115.2 Kbps
115.2 Kbps
Required
Data bits
Setting
Factory Default
Necessity
5, 6, 7, 8
8
Required
When the user sets Data bits to 5 bits, the stop bits setting will automatically change to 1.5 bits.
Stop bits
Setting
Factory Default
Necessity
1, 2
1
Required
Stop bits will be set to 1.5 when Data bits is set to 5 bits.
Parity
Setting
Factory Default
Necessity
None, Even, Odd, Space, Mark
None
Required
5-10