Pre-installation checks, Medium regency large regency, Small regency – Stovax REGENCY 1000 User Manual
Page 16: Ventilation
16
PRe-INsTAllATIoN CHeCKs
Medium
Regency
Large
Regency
Without liner system
round (diameter)
mm
mm
inch
mm
inch
inch
m
feet
4.5
15
4.5
15
200
200
8
180
7
8
200
200
8
180
7
8
Without liner system (square)
minimum dimension
With liner or factory made
system (diameter)
installed in accordance with manufacturers instructions
Flue/Chimney
Size
Flue/Chimney
minimum height*
* When measured from the top of the appliance to the top of the flue, with no horizontal sections
and a maximum of 4 bends with angles of less than 45°
Model
Small Regency - 1000
Medium Regency - 1001
Large Regency - 1002
Small
Regency
200
8
180
7
200
8
4.5
15
1. VeNTIlATIoN
1.1 This appliance requires ventilation to supply combustion air.
Any room containing the appliance must have a permanent
air vent opening with a total free area of at least 50% of the
appliance throat area.
1.2 Increase air supply provisions where a room contains
multiple appliances.
1.3 If vents open into adjoining rooms or spaces there must be
an air vent of at least the same size direct to the outside.
1.4 Permanent air vents should be non-adjustable and
positioned where they are unlikely to become blocked.
1.5 Site the vents where cold draught is unlikely to cause
discomfort. This can be avoided by placing vents near
ceilings or close to the appliance, see Diagram opposite.