-7-

All leak testing must be done with a soapy water solu-

tion or equivalent leak test liquid. Never use a match or

open flame to test for gas leaks. A fire or explosion

could result.

The appliance and its individual shut–off valve must be

disconnected from the gas supply piping system during

any pressure test of that system at test pressures in

excess of 1/2 PSIG (3.5 kPa).

The appliance must be isolated from the gas supply

piping system by closing its individual manual shut–off

valve during pressure testing of the gas supply piping

system at test pressures equal to, or less than 1/2

PSIG (3.5 kPa).

GAS

VALVE

MANUAL GAS

SHUT-OFF

GROUND-JOINT

UNION

SEDIMENT

TRAP

3” - 5”

Figure 7

IV) WATER PIPING

General

Pipes and fittings must be installed as shown in Figure

8. Note that the dip tube is in the cold water fitting (right

hand side) of the heater. Some heaters may have heat

trap fittings installed in the HOT and COLD water con-

nection of the heater. These appear generally like plugs

in the fitting, the cold fitting being colored blue and the

hot fitting, red or pink. Do not attempt to pry these

“plugs” loose or damage them.

When attaching sweat fittings to the heater, do not

apply heat to the nipples of the water heater because

the nipples contain a plastic liner. Sweat the adaptor to

a length of tubing – usually 6” – 8” long minimum,

before fitting the adaptor to the water connections.

Hot and Cold Water Connections

It is good practice to install unions at the hot and cold

water connection of the heater. The cold water connec-

tion must have a shut–off valve installed so that the

heater can be isolated from the house supply for ser-

vicing.

When the water connections have been completed, fill

the tank with water.

To fill the tank, open an upstairs hot water faucet. Open

the cold water valve in the cold water line to the heater.

Make sure the drain valve of the heater is closed. When

an uninterrupted stream of water without apparent air

bubbles flows from the hot water faucet, the tank is

filled. Close the hot water faucet.

Check for leaks, and repair as necessary.

SHUT-OFF VALVE

UNION

PIPE LENGTH 6” - 8”

(150 - 200 mm)

ADAPTOR 3/4” NPT

DIPTUBE

(COLD SIDE ONLY)

WATER PIPING DETAIL

Figure 8

NOTE: VENTING DETAILS

HAVE BEEN REMOVED

FOR CLARITY

Temperature and Pressure Relief Valve

Water heaters have the temperature and pressure relief

valve factory–installed for protection against excessive

temperature and/or pressure.

Any replacement valve must not exceed the tempera-

ture and pressure rating of the original valve, and must

meet the latest edition of ANSI Z21.22 • CSA 4.4 the

Standard for “Relief Valves and Automatic Gas Shutoff

Devices for Hot Water Supply Systems.”

To prevent bodily injury, hazard to life or damage to

property, the relief valve must be allowed to discharge

water in the event of excessive temperature and/or

pressure in quantity, should circumstances demand.

CAUTION

Before filling the tank, ensure that a properly rated

temperature and pressure relief valve is installed in

the designated fitting.

See following T&P Valve section.