Method of installation, B) air from outdoors, Venting materials – GSW Gas Fired Water Heater User Manual

Page 5: Venting connections, Outside vent terminal location

background image

-3-

(b) Air from Outdoors

A confined space shall be provided with two permanent

openings: one near the top, and one near the bottom of

the enclosure. These openings can be open directly to

the outdoors or by ducts to crawl spaces or attics which

are open to the outdoors.

(i) Air Supplied from Outdoors,

Table II, see Figure 2

Free

Area A

D

L

D

U

H

W

CSA B149.1

1 in

2

per 4000 BTU/Hr

6” Min., 18” Max

Note 1

3” min.

per calculation from A

U.S. ANSI Z223.1

1 in

2

per 4000 BTU/Hr

12” min.

12” min.

3” min.

per calculation from A

Table II

(ii) Air Supplied from Outdoors by Horizontal Ducts

Table III, see Figure 2

Free

Area A

D

L

D

U

H

W

CSA B149.1

1 in

2

per 2000 BTU/Hr

6” Min., 18” Max

Note 1

3” min.

per calculation from A

U.S. ANSI Z223.1

1 in

2

per 2000 BTU/Hr

12” min.

12” min.

3” min.

per calculation from A

Table III

(iii) Air Supplied from Outdoors by Vertical Ducts,

Table IV, see Figure 2

Free

Area A

D

L

D

U

H

W

CSA B149.1

1 in

2

per 4000 BTU/Hr

6” Min., 18” Max

Note 1

3” min.

per calculation from A

U.S. ANSI Z223.1

1 in

2

per 4000 BTU/Hr

12” min.

12” min.

3” min.

per calculation from A

Table IV

METHOD OF INSTALLATION

Venting Materials

Vent Pipe Material of Schedule 40 ABS, CPVC must

be used in this installation.

All materials must be of the same type for one instal-

lation and must use the appropriate solvent cement

and primer/cleaner.

Pipes and Fittings must conform to the following stan-

dards:

i) CSA standard and/or

ii) American National Standards Institute and the

American Society for Testing and Materials

(ANSI /ASTM) Standards.

VENTING CONNECTIONS

1) VENT TERMINATION

Outside Vent Terminal Location

In Canada, the vent terminal location must be in accor-

dance with the latest edition of the CSA B149.1.

Natural Gas and Propane Installation Code and Public

Utility and/or Local Codes having jurisdiction.

In the U.S., the National Fuel Gas Code, ANSI Z 223.1

(latest edition) and local codes have specific require-

ments for the location of vent terminals on vertical

walls.

The following is a condensed outline for prohibited

locations of outside vent terminals:

In Canada:

The vent shall not terminate:

within 6’ of a mechanical air supply inlet of a build-

ing.

above a meter regulator within 3’ horizontally of the

vertical centre line of the regulator.

vent outlet to a maximum vertical distance of 15’.

less than 1’ above grade level or the highest snow

accumulation level that can be expected. In areas

where high snow accumulations occur, the vent ter-

minal may have to be raised by a vertical riser.

within 1’ of a building opening or combination air

inlet of another appliance.

less than 7’ above a driveway or sidewalk.