beautypg.com

Aw h d – GSW Gas Fired Water Heater User Manual

Page 4

background image

-2-

SAFETY WARNING

Water heaters are heat producing appliances. To
avoid damage or injury, there shall be no materials
stored against the water heater and proper care shall
be taken to avoid unnecessary contact (especially by
children) with the water heater.

INSTALLATION CLEARANCES

The minimum clearances between the heater and

combustible material are:

Sides and Rear

1”

Flue Pipe

0”

Jacket Top to Ceiling

8” *

Flue Pipe Through Wall

0”

*

For 40 and 50 gallon models, it is recommended

that a 36” clearance from jacket top to ceiling be

maintained in order to have sufficient room for

anode replacement should this become neces-

sary. For 60 gallon models, a 42” clearance is rec-

ommended.

This water heater is certified for installation on a com-

bustible floor.

A minimum clearance of 24" in front should be provid-

ed for inspection and servicing.

This heater is approved for alcove and closet type

installation, but maintain the minimum clearances to

combustible material listed above.

II) VENTING

COMBUSTION AIR SUPPLY

An adequate air supply shall be provided for combus-

tion and ventilation. An insufficient supply of air will

cause recirculation of combustion products resulting in

air contamination that may be hazardous to life.

When an exhaust fan is installed in the same room with

this water heater, sufficient openings for air must be

provided. Undersized openings will cause air to be

drawn into the room through the exhaust vent.

Unconfined Spaces

In unconfined spaces in buildings of other than unusu-

ally tight construction, infiltration may be adequate to

provide air for combustion, ventilation and dilution of

flue gases. Unconfined space is defined as a space

whose volume is not less than 50 cubic feet per 1,000

BTU/hour of the combined input rating of all appli-

ances installed in that space. Rooms directly adjoining

the space in which the appliances are installed,

through openings and not furnished with doors, are

considered part of the unconfined space.

Confined Spaces

(Less than 50 cubic feet per 1,000 BTU/hour)

(a) Air from Inside the Building.

See Table I and Figure 2.

Table I Confined Space

Dim.

A

D

L

D

U

H

W

CSA B149.1

1 in

2

per 1000 BTU/Hr

6” Min., 18” Max

Note 1

3” min.

per calculation from A

U.S. ANSI Z223.1

1 in

2

per 1000 BTU/Hr

12” or less

12” or less

3” min.

per calculation from A

NOTE 1: The upper opening shall be located as near

the ceiling as possible, but not lower than any relief

opening of a draft hood or draft regulator. It shall have

a free area not less than the total area of all vents or

chimneys from the appliances within the room, except

for closet type installations where the area shall not

be less than that of the lower opening.

H

D

U

A

W

H

D

L

A

W

Figure 2

FOR YOUR SAFETY

Do not store or use gasoline or other

flammable, combustible, or corrosive

vapours and liquids in the vicinity of

this or any other appliance.

WARNING

THE FLOW OF COMBUSTION AND VEN-

TILATION AIR MUST NOT BE

OBSTRUCTED.