Airflow data, Irflow – Goodman Mfg SS-GPH13MC User Manual
Page 12

12
www.goodmanmfg.com
SS-GPH13MC
SS-GPH13MC
www.goodmanmfg.com
13
P
roduct
S
PecificationS
P
roduct
S
PecificationS
a
irflow
d
ata
Model
Speed
Volts
E.S.P (In. of H₂O)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
GPH13
36M43*
Low
230
CFM
1122
1078
1032
972
915
804
687
558
Watts
338
330
321
310
300
283
264
250
Med
230
CFM
1387
1331
1264
1209
1119
1041
935
748
Watts
456
440
428
412
399
382
363
330
High
230
CFM
1521
1454
1388
1311
1230
1144
1055
939
Watts
534
521
510
490
477
461
442
420
GPH13
48M43*
T1 (G)
230
CFM
1,440
1,395
1,360
1,310
1,265
1,235
1,190
1,130
Watts
275
285
295
315
325
335
345
355
T2 / T3
(W2)
230
CFM
1,795
1,765
1,715
1,695
1,650
1,600
1,500
1,375
Watts
475
490
505
520
530
535
510
475
T4 / T5 (Y)
230
CFM
1,860
1,820
1,785
1,745
1,700
1,625
1,515
1,395
Watts
515
530
545
565
570
550
535
485
GPH13
60M43*
T1 (G)
230
CFM
1,755
1,720
1,685
1,645
1,615
1,570
1,530
1,465
Watts
420
435
455
460
475
490
500
500
T2 / T3
(W2)
230
CFM
1,850
1,820
1,775
1,735
1,705
1,675
1,610
1,495
Watts
480
500
515
525
535
555
545
520
T4 / T5 (Y)
230
CFM
2,180
2,125
2,050
1,975
1,875
1,800
1,655
1,530
Watts
770
755
725
700
675
640
575
540
Notes:
• Data shown is dry coil. Wet coil pressure drop is approximately 0.1" H₂O, for two-row indoor coil; 0.2” H₂O, for three-row indoor coil; and 0.3” H₂O, for four-
row indoor coil.
• Data shown does not include filter pressure drop, approx. 0.08” H2O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM. See Repair Parts list.
• Reduce airflow by 2% for 208-volt operation.