Product specs, Roduct, Pecifications – Goodman Mfg GPH14H User Manual
Page 3

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-GPH14H
www.goodmanmfg.com
3
S
pecificationS
GPH14
24H41A*
GPH14
24H41C*
GPH14
30H41A*
GPH14
30H41C*
GPH14
36H41A*
GPH14
36H41C*
Cooling Capacity
AHRI Cooling Capacity (BTU/h)
24,000
24,000
28,400
28,400
36,000
36,000
Sensible BTU/h
18,200
18,200
23,400
23,400
27,400
27,400
SEER / EER
14.5 / 12.0
14.5 / 12.0
14.0 / 12.0
14.0 / 12.0
14.0 / 11.5
14.0 / 11.5
Decibels
76
76
76
76
78
78
AHRI Numbers
4385132
5677874
4385133
5677875
4385134
5677876
Heating Capacity
BTU/h (47°F)
22,800
22,800
27,600
27,600
32,200
32,200
C.O.P. (47°F)
3.8
3.8
3.8
3.8
3.7
3.7
BTU/h (17°F)
13,000
13,000
15,400
15,400
20,400
20,400
C.O.P. (17°F)
2.4
2.4
2.5
2.5
2.4
2.4
HSPF
8.0
8.0
8.0
8.0
8.0
8.0
Evaporator Motor
Type
EEM
EEM
EEM
EEM
EEM
EEM
Wheel (D x W)
10 x 8
10 x 8
10 x 8
10 x 8
10 x 8
10 x 8
Cooling CFM
875
875
1,050
1,050
1,200
1,200
Fan-Only CFM
800
800
950
950
1,100
1,100
RLA
1.5
1.5
1.86
1.86
1.86
1.86
No. of Speeds
5
5
5
5
5
5
Horsepower - RPM
½ - 1,050
½ - 1,050
½ - 1,050
½ - 1,050
½ - 1,050
½ - 1,050
Evaporator Coil
Face Area (ft
2
)
5.25
5.2
4.67
5.2
5.2
6.2
Rows Deep/ Fins per Inch
3/ 16
3/ 14
4/ 16
3/ 14
3/ 14
3/ 14
Indoor Metering Device Size
0.057
0.061
0.065
0.065
0.068
0.068
Filter Size (ft
2
)
20 x 20 x 1
20 x 20 x 1
20 x 25 x 1
20 x 25 x 1
25 x 25 x 1
25 x 25 x 1
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
Refrigerant Charge (oz.)
85
105
105
105
125
125
Condenser Fan / Coil
Horsepower - RPM
1/6 - 815
1/6 - 815
1/6 - 815
1/6 - 815
¼ - 1075
¼ - 1075
RLA/LRA
1.1 / 1.7
1.1 / 1.7
1.1 / 1.7
1.1 / 1.7
1.5 /3.0
1.5 /3.0
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 4
22 / 4
Face Area (ft
2
)
13.4
13.4
13.4
13.4
17
17
Outdoor Metering Device Size
0.049
0.047
0.047
0.047
0.067
0.063
Rows Deep/ Fins per Inch
1 / 24
1 / 24
1 / 24
1 / 24
1 / 24
1 / 24
Compressor
Quantity / Type
1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single
Compressor RLA/LRA
12.8 / 58.3
12.8 / 58.3
14.1 / 73
14.1 / 73
16.7 / 79
16.7 / 79
Electrical Data
Voltage/Phase/ Frequency
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
Indoor Blower FLA
1.5
1.5
1.86
1.86
1.86
1.86
Outdoor Fan RLA
1.1
1.1
1.1
1.1
1.4
1.4
Total Unit Amps
15.4
15.4
17.06
17.06
19.96
19.96
Min. Circuit Ampacity¹
18.6
18.6
20.6
20.6
24.2
24.2
Min. Overcurrent Protection (amps)²
30
30
30
30
40
40
Operating & Ship Weights (lbs)
315 / 325
315 / 325
315 / 325
315 / 325
375 / 385
375 / 385
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.