Heat kit electrical data, Lectrical, Roduct – Goodman Mfg GPH14H User Manual
Page 21: Pecifications, Lower

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-GPH14H
www.goodmanmfg.com
21
H
eat
K
it
e
lectrical
D
ata
(B
lower
o
nly
, H
eat
M
oDe
)
Model and
Heat Kit Usage
Circuit #1
Circuit #2
Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹
MOD²
MCA¹
MOD²
MCA¹
MOP²
GPH1424H41**
1.9
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
43
50
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
55
60
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
68
70
9.5 / 32,400
GPH1430H41**
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
45
50
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
57
60
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
70
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
95
100
14.25 / 48,600
GPH1436H41**
2.3
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
49
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
61
70
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
74
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
98
100
14.25 / 48,600
GPH1442H41**
3.6
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
51
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
63
70
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
76
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
101
110
14.25 / 48,600
HKP-20C
43 / 49
45 / 50
43 / 49
45 / 50
128
150
19.0 / 64,800
GPH1448H41**
3.6
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
54
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
66
70
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
79
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
103
110
14.25 / 48,600
HKP-20C
43 / 49
45 / 50
43 / 49
45 / 50
131
150
19.0 / 64,800
GPH1460H41**
7.5
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
62
80
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
74
90
7 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
87
100
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
112
125
14.25 / 48,600
HKP-20C
43 / 49
45 / 50
43 / 49
45 / 50
139
150
19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
HKP-15C and HKP-20C replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.