Roduct, Pecifications – Goodman Mfg SS-CPKF50 User Manual
Page 3

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-CPKF50
www.goodmanmfg.com 3
2 www.goodmanmfg.com
SS-CPKF50
S
PecificationS
CPKF24-2*
CPKF36-2*
CPKF36-5*
CPKF42-5*
CPKF48-5*
CPKF60-5*
CPKF61-5*
Capacities
Nominal Cooling (BTU/h)
23,600
33,000
35,000
40,000
48,000
53,000
57,000
EER¹
9.0
9.0
9.0
9.0
9.0
9.0
9.0
Nominal Heating (BTU/h)
23,000
32,000
32,000
39,000
48,000
54,000
61,000
Decibels
78
78
78
78
78
80
80
Compressor
RLA
12.2
17.9
5.3
7.4
9.0
9.0
10.9
LRA
64
97.4
42
50
65.5
74
101
Volts
220-240
220-240
380-420
380-420
380-420
380-420
380-420
Condenser Fan Motor
Horsepower
¼
¼
⅓
¼
⅓
⅓
⅓
FLA
0.9
0.9
1.2
0.8
1.2
1.2
1.2
Volts
220-240
220-240
380
380
380
380
380
Refrigeration System
Liquid Valve Size (“O.D.)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Suction Valve Size (“O.D.)
¾
¾
¾
⅞
⅞
⅞
⅞
Valve Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge (oz.)
72
110
110
131
137
138
167
Shipped with Orifice Size (in.)
0.059
0.073
0.073
0.080
0.084
0.093
0.093
Condenser Fan / Coil
Horsepower - RPM
¼-950
¼-950
⅓-1075
¼-950
⅓-1075
⅓-1075
⅓-1075
Fan Diameter/ # Fan Blades
20/3
20/3
20/3
22/3
22/3
22/3
22/3
Outdoor Nominal CFM
1800
1800
1800
2600
2600
2600
3200
Face Area (ft²)
13.3
14.58
14.58
14.58
17
17
1
Rows Deep/ Fins per Inch
1/19
1/19
1/19
1/19
1/19
1/22
1/22
Fin Type
Ripple
Ripple
Ripple
Ripple
Ripple
Ripple
Ripple
Coil No. of Tubes
22
24
24
24
24
36
36
Coil Tube Diameter (in.)
0.375
0.375
0.375
0.375
0.375
0.375
0.375
Electrical Data
Voltage-Hz / Phase
220/240-50/1
380/415-50/3
Min. Circuit Ampacity²
16.2
23.3
7.9
10
12.4
12.4
14.8
Max. Overcurrent Protection ³
25 amps
40 amps
15 amps
15 amps
20 amps
20 amps
25 amps
Min / Max Volts
198/264
198/264
342/456
342/456
342/456
342/456
342/456
Power Supply Conduit Size
½ or ¾
½ or ¾
½ or ¾
½ or ¾
½ or ¾
½ or ¾
½ or ¾
Ship Weight (lbs-[kg])
191 (87)
206 (94)
206 (94)
213 (97)
216 (98)
248 (113)
249 (113)
¹ Energy Efficiency Ratio
² Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.