Duct smoke detector wiring diagrams, Rrl/oci w/ ep switch, Rrl w/ ep switch – Greenheck Fan DH100ACDCLP User Manual
Page 7

L2
WHITE
L1
BLAC
K
ORANG
E
BLUE
BLAC
K
DH100ACDCLP DUCT DETECTOR
115 VAC
RED
RRL
15
5
12
11
2
1
14
13
3 4
18
8
16 17
6 7
19 20
9 10
C
A B
YELLOW
YELLOW
YELLOW
YELLOW
SWITCH #1
SWITCH #2
DH100ACDCLP DUCT DETECTOR
BLUE
RED
WHITE
24 VAC/VDC
WHITE
12
11
14
13
1 2 3 4 5
15
18
16 17
19 20
8
6 7
9 10
C
A B
RED
RED
E/P SWITCH
OPTIONAL
THIRD E/P SWITCH
OPTIONAL
SECOND E/P SWITCH
RED
RED
WHITE
E/P SWITCH
RED
WHITE
E/P SWITCH
RED
BLAC
K
BLAC
K
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
B C
A
9 10
6 7
4 5
2 3
1
8
19 20
17
14 15 16
12 13
11
18
WHITE
RED
BLUE
220/240 VAC
DH100ACDCLP DUCT DETECTOR
RRL/OCI W/ EP Switch
L2
WHITE
L1
BLAC
K
ORANG
E
BLUE
BLAC
K
DH100ACDCLP DUCT DETECTOR
115 VAC
RED
RRL
15
5
12
11
2
1
14
13
3 4
18
8
16 17
6 7
19 20
9 10
C
A B
DH100ACDCLP DUCT DETECTOR
BLUE
RED
WHITE
24 VAC/VDC
WHITE
12
11
14
13
1 2 3 4 5
15
18
16 17
19 20
8
6 7
9 10
C
A B
RED
RED
E/P SWITCH
OPTIONAL
THIRD E/P SWITCH
OPTIONAL
SECOND E/P SWITCH
RED
RED
WHITE
E/P SWITCH
RED
WHITE
E/P SWITCH
RED
BLAC
K
BLAC
K
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
B C
A
9 10
6 7
4 5
2 3
1
8
19 20
17
14 15 16
12 13
11
18
WHITE
RED
BLUE
220/240 VAC
DH100ACDCLP DUCT DETECTOR
RRL W/ EP Switch
DUCT SMOKE DETECTOR
WiRiNg DiAgRAMS