Duct smoke detector wiring diagrams, Fusible link – Greenheck Fan DH100ACDCLP User Manual
Page 4

OPTIONAL
SECOND MOTOR
L2
MOTOR
WHITE
MOTOR
L1
BLUE
BLAC
K
DH100ACDCLP DUCT DETECTOR
115 VAC
RED
15
5
12
11
2
1
14
13
3 4
18
8
16 17
6 7
19 20
9 10
C
A B
BLAC
K
WHITE
WHITE
MOTOR
BLAC
K
OPTIONAL
THIRD MOTOR
DH100ACDCLP DUCT DETECTOR
BLUE
RED
WHITE
24 VAC/VDC
WHITE
12
11
14
13
1 2 3 4 5
15
18
16 17
19 20
8
6 7
9 10
C
A B
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
C
B
A
10
20
8 9
7
6
18
16 17
19
4
2 3
14
12 13
11
1
15
5
WHITE
RED
BLUE
220/240 VAC
DH100ACDCLP DUCT DETECTOR
Fusible Link
DUCT SMOKE DETECTOR
WiRiNg DiAgRAMS
OPTIONAL
SECOND MOTOR
L2
MOTOR
WHITE
MOTOR
L1
BLUE
BLAC
K
DH100ACDCLP DUCT DETECTOR
115 VAC
RED
OCI
15
5
12
11
2
1
14
13
3 4
18
8
16 17
6 7
19 20
9 10
C
A B
YELLOW
YELLOW
YELLOW
YELLOW
SWITCH #1
SWITCH #2
BLAC
K
WHITE
WHITE
MOTOR
BLAC
K
OPTIONAL
THIRD MOTOR
DH100ACDCLP DUCT DETECTOR
BLUE
RED
WHITE
24 VAC/VDC
WHITE
12
11
14
13
1 2 3 4 5
15
18
16 17
19 20
8
6 7
9 10
C
A B
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
DH100ACDCLP DUCT DETECTOR
220/240 VAC
BLUE
RED
WHITE
20
13
11 12
15
14
18
16 17
19
10
3
1 2
5
4
8
7
6
9
B
A
C
OCI