Greenheck Fan Duct Smoke Detector none User Manual
Installation instruction, Detail 1, For rrl (resettable/reusable link) on

Gasket
1 Req’ d
J-Box Cover
1 Req’ d
#10 1/2 in.
Te k
Scr ew
2 Req’ d
J-Box
1 Req’ d
RRL
Req’ d
3
2
4
6
Steps to install an RRL in a Fire Smoke Damper:
1) Drill/Saw a 3 5/8 in. (92mm) diameter hole in sleeve (Detail
2).
2) Insert OCI unit through hole in sleeve (round end inside).
3) Place 4 x 4 in. J-Box over the flange of the OCI unit and
align holes.
4) Mount control box to sleeve/sideplate with #10-16 x 3/4 in.
(19mm) TEK screw (or equivelant) (Detail 1).
5) Complete wiring and install J-Box cover.
Part Number 459840
Detail 1
Installation Instruction
for RRL (resettable/reusable link) on
FSD, SSFSD, SEFSD, IMO series
Combination Fire Smoke Dampers