Lighting the boiler, Initial lighting – Glowworm Lighting ULTRACOM CXI User Manual

Page 10

background image

www.glow-worm.co.uk

10

Initial Lighting

Remove the cover plate, refer to the fault finding section on

page 15 and diagram 8.

Check that all isolating valves and the gas service cock on

the appliance are open and that water flows from the hot

water taps, then close taps, refer diagram 3.

Note:

If you are in any doubt about the boiler being filled

with water contact your installer or Glow-worm's own

service organisation using the telephone number on the

inside front cover of this booklet.

Do not operate the boiler without water.

1.

With no demand from any external controls, switch on

the electrical supply to the boiler.

Lighting the Boiler

Note:

If the electrical supply has been interrupted for any

reason, you may need to set the clock and day before

continuing, refer to diagram 5.

2.

Select your required function, refer to diagram 9, press

"Mode" repeatedly to scroll through your options and select

one of the following:-

Timed central heating with domestic hot water.

Constant central heating with domestic hot water.

Domestic hot water only.

Boiler functions ALL switched off.

3.

Turn ON your external controls and select the room

temperature required.

The boiler will operate automatically.

Note:

The display will indicate the Heating system

pressure in bar or:

Water temperature, when heating is on.

Domestic Hot Water temperature setpoint, when

there is a demand.

Fault Code (see section Fault Finding)

13469

Diagram 3

A

- Central Heating Isolation V

alve

B

- Domestic Hot W

ater

C

- Gas Service Cock

D

- Domestic Cold W

ater

E

- Condensate drain

F

- Double Check Inlet V

alve

G

- Safety Discharge V

alve