FieldServer Canatal Satchnet Driver FS-8700-59 User Manual
Page 17
![background image](/manuals/106357/17/background.png)
FS-8700-59 Canatal Driver Manual
Page 17 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Error #
Message
Description
CANA:#11
Error. Poll(%d)/Response(%d) Address
Not Equal
The address polled has responded but as a different
address. The response will be abandoned. This may mean
that the device's address has been incorrectly set or that
the device is not functioning correctly.
CANA:#12
Error.
Response
Expected(%d)/Actual(%d) Bytes
The data was requested from a table with mixed data
formats and the data served was not in Byte (default)
format. Use the Cana_Format parameter to override the
Data Format in the CSV file.
CANA:#13
Error. Array is too small for
mapDesc=<%s> Some data will not be
stored.
This is regarded as an error as the Map Descriptor has
requested more data than can be stored. The excess data
has been discarded. Modify the Map Descriptor definition
or change the array length in the CSV file and restart the
FieldServer.
CANA:#14
Error. Unknown Data method (%d) for
mapDesc=<%s>
Report this error to FIELDSERVER TECHNOLOGIES.
CANA:#15
Error. Unknown Data method (%d) for
mapDesc=<%s>
CANA:#16 Error. Ack Expected