beautypg.com

Frymaster 24G Series User Manual

Page 27

background image

24G SERIES FLATBOTTOM GAS FRYERS

CHAPTER 3: INSTALLATION INSTRUCTIONS

3-12

3.7 Gas Conversion Procedures (cont.)


CE UNITS ONLY:

When converting from G20 to G25 gas, the following procedures apply:

Equipment replacement is not required.

Adjust orifice gas pressure to the appropriate value listed in the table on page 3-9 by turning
the gas valve "adjustment screw".

After adjustment, replace the adjustment-screw cover.


When converting from G20 (or G25) gas to propane/LP G31 (or vice-versa) gas, the following
procedures apply:

Burner orifices and pilot orifice MUST be replaced.

Adjust orifice gas pressure to the appropriate value listed in the table on page 3-9 by turning
the gas-valve adjustment screw.

After adjustment, replace the adjustment-screw cover.

Factory MUST be notified so the conversion can be documented and a new rating plate can
be sent out.


When converting from G20 (20 mbar) to G25 (25 mbar), or vice-versa, or G31 (37 mbar) to G31 (50
mbar), the following procedures apply:

Check pilot-adjustment and adjust as necessary.

Other adjustments are not necessary.


Conversion from one gas family to another (i.e. changing from natural gas to propane) requires
special components. Obtain the necessary components using the cross-reference in Section 3.8, Gas
Conversion Components.

Conversions can only be executed by qualified, factory-authorized personnel
.