Hardware connection Tips/Hints

Follow standard RS-485 2-wire guidelines for installation. See connection diagram below.

R1

-

+

FieldServer

GND

100

1/2 W

TD(A)

TD(B)

RD(A)

RD(B)

GND

485SDD16

TD(A)

TD(B)

RD(A)

RD(B)

GND

485SDD16

100

1/2 W

100

1/2 W

RS-485 2-wire Connection

Connection Notes

The x25 and the QuickServer do not support being configured as a BACnet MSTP client on one port and a BACnet
MSTP server on another port at the same time. The x40 and the x30 support this.

In order for this to work the BACnet MSTP server section must be configured first.