Appendix b.4. bacnet specific error messages, Appendix b.5. bacnet error response decoding, Appendix b.5.1 – FieldServer FS-8700-73 User Manual

Page 35: Bacnet error class

background image

FS-8700-73 BACnet MSTP Driver Manual

Page 35 of 48

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.FieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]

Stat

Description

Resolution

Link Control

A “who-is” link control message was
send or received.

It is normal to receive a few link control
messages. If the number is higher than the
transmit/receive messages, however, there may
be a problem with lost communications..

Unsupported
Properties

A request for an unsupported property
was received

This is not an error. BACnet clients often poll all
properties of a particular object to determine
which properties are supported.

Segmentation
Not Supported

Data was requested but the response
would have exceeded the maximum size
of the APDU and could not be sent using
an un-segmented message.

This is not an error - the BACnet client will use a
different method to read data from the
FieldServer.

Sequence Error

Invoke ID of a reply did not match the
Invoke ID of the poll.

You should not see this message. It normally
indicates a configuration error.

Write

Access

Denied

A write to an object was denied.

This typically happens when trying to write to an
Input Object that is not Out-Of-Service. It is not
possible to write to Input Objects.

Exception Errors

A BACnet Service was denied because it
is not supported

Consult the PIC statement to determine what
services are supported.

Appendix B.4. BACnet Specific Error Messages

Message
Description

Cause

Suggested Resolution

Bacnet

IP

DLL

Temporarily out of
receive buffers

The FieldServer was flooded with more BACnet IP packets
than it could handle. This typically occurs when a
workstation discovers a large network resulting in many
Who-Is and I-Am broadcasts. The FieldServer will recover
from this, but some timeout errors could result.

Take action only if the error
is continuous in which case
the network load must be
analyzed and corrected.

Appendix B.5. BACnet Error Response Decoding

BACnet reports errors in the following format:

T02> 10/22 02:57 HEXDUMP : ERROR_PDU
T02> 10/22 02:57 0x19d2d 50 97 0f 91 02 91 2a
T02> 10/22 02:57 BACnet -> Unexpected ERROR_PDU : err_class=2 err_code=42


These can be decoded using the following tables:

Appendix B.5.1.

BACnet Error CLASS

Device

0

Object

1

Property

2

Resources 3
Security

4

Services

5