beautypg.com

Venting installation – FMI (V)S36 User Manual

Page 9

background image

www.fmiproducts.com

111026-01G

9

Venting installatiOn

Continued

14

3

/

8

"

(36.5 cm)

30"

(76.2 cm)

1"

(2.5

cm)

1"

(2.5

cm)

Minimum Measurements

1"

(2.5 cm)

Opening "A"

Pitch

Slope Opening "A"

Max.

Used Flashing

Model No.

Flat

15"

V6F-8DM

0-6/12

26.6°

16

1

/

8

"

V6F-8DM

6/12-

12/12

45.0°

20

3

/

8

"

V12F-8DM

FLASHING INSTALLATION (V6F-8DM

OR V12F-8DM)

Determine the flashing to be used with the roof

opening chart. Slide flashing over pipe until

base is flat against roof. Replace as many

shingles as needed to cover exposed area

and flashing base. Secure in position by nail-

ing through shingles (see Figure 13). DO NOT

NAIL THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof

When installing flashing on a metal roof, it is

required that putty tape be used between the

flashing and roof. The flashing must be secured

to the roof using #8 x 3/4" screws and then

sealed with roof coating to prevent leakage

through screw holes. A roof coating must also be

applied around perimeter of flashing to provide

a proper seal.

Figure 12 - Roof Opening Measurements

Nail Only

Outer

Perimeter

of Flashing

Storm Collar

Flashing

Cone

Underlap Shingles

at Bottom

Overlap

Shingles Top

and Sides Only

Figure 13 - Flashing Installation

Storm Collar Installation (SC1 or SC2)

Place storm collar over pipe and slide down

until it is snug against the open edge of the

flashing (see Figure 14). Use SC1 for all round

terminations and SC2 for all terminations with

slip sections. Apply waterproof caulk around the

perimeter of the collar to provide a proper seal.

Figure 14 - Storm Collar

Chimney

Pipe

Waterproof

Caulk

Storm

Collar

Flashing

Terminations/Spark Arrestor

The fireplace system must be terminated with

the listed round top or chase terminations. In

any case, refer to the installation instructions

supplied with the termination. The termination

approved for this fireplace are the RT-8DM and

RTL-8DM that can be used for flashing or chase

and ET-8DM, ETO-8DM, ETL-8DM and ETLO-

8DM for chase style termination only. Figure 15

shows an RTL-8DM round top termination.

CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions

provided with the termination

being used.

Attach Bracket

Tabs to

Outer Pipe

(3 Places)

Secure with

Screws

RTL-8D

Level of

Flue Gas

Outlet

Caulk

Collar

Flashing

Underlap

Shingles

Bottom Only

Figure 15 - Termination

Overlap

Shingles Top

and Sides