Warning, Caution – Friedrich HAZARDGARG R-410A User Manual

Page 21

background image

3. After all refrigerant has been recovered, disconnect

suction and discharge lines from the compressor and

remove compressor. Be certain to have both suction

and discharge process tubes open to atmosphere.

4. Carefully pour a small amount of oil from the suction

stub of the defective compressor into a clean

container.

9. Evacuate the system with a good vacuum pump capable

of a final vacuum of 200 microns or less. The system

should be evacuated through both liquid line and suction

line gauge ports. While the unit is being evacuated, seal

all openings on the defective compressor. Compressor

manufacturers will void warranties on units received not

properly sealed. Do not distort the manufacturers tube

connections.

10. Recharge the system with the correct amount of

refrigerant. The proper refrigerant charge will be

found on the unit rating plate. The use of an accurate

measuring device, such as a charging cylinder,

electronic scales or similar device is necessary.

5. Using an acid test kit (one shot or conventional kit), test

the oil for acid content according to the instructions

with the kit.

6. If any evidence of a burnout is found, no matter how

slight, the system will need to be cleaned up following

proper procedures.

7. Install the replacement compressor.

8. Pressurize with a combination of R-410A and nitrogen

and leak test all connections with an electronic or

Halide leak detector. Recover refrigerant and repair

any leaks found.

Repeat Step 8 to insure no more leaks are present.

The use of nitrogen requires a pressure

regulator. Follow all safety procedures and

wear protective safety clothing etc.

Failure to follow proper safety procedures

result in serious injury or death.

WARNING

EXPLOSION HAZARD

Proper safety procedures must be followed,

and proper protective clothing must be worn

when working with liquid refrigerant.

Failure to follow these procedures could

result in minor to moderate injury.

CAUTION

FREEZE HAZARD

20

ELECTRIC SHOCK HAZARD

WARNING

Turn off electric power before service or

installation.

Failure to do so may result in personal injury,

or death.

Sealed Refrigeration System contains refrigerant

and oil under high pressure.

Proper safety procedures must be followed,

and proper protective clothing must be worn

when working with refrigerants.

Failure to follow these procedures could

result in serious injury or death.

WARNING

HIGH PRESSURE HAZARD

The use of nitrogen requires a pressure

regulator. Follow all safety procedures and

wear protective safety clothing etc.

Failure to follow proper safety procedures

result in serious injury or death.

WARNING

EXPLOSION HAZARD

1.

2.

3.

4.

5.

Recover all refrigerant and oil from the system.

Remove compressor, capillary tube and filter drier

from the system.

Flush evaporator condenser and all connecting

tubing with dry nitrogen or equivalent. Use approved

flushing agent to remove all contamination from

system. Inspect suction and discharge line for

carbon deposits. Remove and clean if necessary.

Ensure all acid is neutralized.

Reassemble the system, including new drier strainer

and capillary tube.

Proceed with step 8-10 on previous section.

SPECIAL PROCEDURE IN THE CASE OF MOTOR

COMPRESSOR BURNOUT