RANGE: Thermostat

(Part No. 618-225-02)

60

° F ( ± 2° ) to 90° F( ± 4° )

SENSING

BULB LOCATION

THERMOSTAT

A cross ambient thermostat is used to maintain the

desired comfort level. The thermostat reacts only to a

change in temperature at the bulb location. Important to

the successful operation of the unit is the position of the

sensing bulb in relation to the evaporator.

TESTING THE THERMOSTAT

Remove the wires from the thermostat. Turn the

thermostat to its coldest position. Check to see if there is

continuity between the two terminals. Turn the thermostat

to its warmest position. Check continuity to see if the

thermostat contacts open.

Note: The temperature must be within the range listed to

check the thermostat. Refer to the troubleshooting section

in this manual for additional information on thermostat

testing.

The HazardGard unit is designed to operate at low outside

ambient temperatures. This is accomplished by the use

of a bypass valve installed in the refrigeration circuit.

The valve is connected between the discharge line at

the compressor and the suction process tube. The valve

responds to suction pressure which, when reduced in the

system, causes the valve to open and bypass hot gas

from the high pressure side to the low pressure side of

the system. The hot gas entering the compressor mixes

with the cool gas returned through the suction line, thus

increasing the suction pressure. The valve is preset to

open when the suction pressure reaches 50 psig. This

pressure setting cannot be altered. The system can be

operated at outdoor temperatures as low as 45

°F before

the evaporator coil will begin to accumulate frost.

To determine if the valve operates, block the return air to

the evaporator coil. Turn on the unit and touch the tube

at the bypass valve outlet which connects to the suction

process tube. When the low side pressure reaches

approximately 50 psig, the valve will begin to open and

the tube will get hot. This method will determine if the

valve is responding to the suction pressure change.

LOW AMBIENT BYPASS VALVE

ELECTRIC SHOCK HAZARD

WARNING

Disconnect power to the unit before

servicing. Failure to follow this warning

could result in serious injury or death.

Sealed Refrigeration System contains

refrigerant and oil under high pressure.

Proper safety procedures must be followed,

and proper protective clothing must be

worn when working with refrigerants.

Failure to follow these procedures could

result in serious injury or death.

WARNING

HIGH PRESSURE HAZARD

LOW AMBIENT

BYPASS VALVE

12