Digital control user input confi guration, Dip switch setting, Factory dip switch confi guration – Friedrich HEAT PUMPS User Manual

Page 16

background image

16

920-087-04

Digital Control User Input Confi guration

The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible
and accessible with the front cover removed from the PTAC.

Dip Switch Setting

1) Electronic Temperature Limiting – Switches 1-4

The digital control is set from the factory to allow a tempera-
ture range between 60°F and 90°F in both heating and cooling
mode. Dip Switches 1-4 can be used to set high and low limits
for either heating or cooling or both.

From the factory all four switches are in the up ‘ON’ position.
The charts to the right show the available electronic limiting
ranges.

2) Fan Cycle Control – Switch 5

All PTACs are shipped from the factory with Dip Switch 5 in the
OFF’ position to cycle the fan only when there is a demand for
the compressor or heater. As an option the fan may be set to
‘continuous’ mode by switching Dip Switch 5 to ‘ON’ position to
run the fan continuously while the unit is powered on.
To ensure that the room temperature is maintained evenly while
in fan cycle mode the Even Temp Load Anticipation feature is
enabled. Quiet Fan Delay is also enabled in fan cycle mode to
lessen the acoustical change between compressor start up and
shut off by running the fan for 5 seconds before each demand
cycle, and 30 seconds after cooling or 15 seconds after heating
cycles.

3) Room Freeze Protection – Switch 6

Units are shipped from the factory with the room freeze protection
disabled. Room Freeze Protection can be switched on at the
owner’s preference by moving Dip Switch 6 to ‘ON’. This feature
will monitor the indoor room conditions and in the event that the
room falls below 40°F the unit will cycle on high fan with the
electric heater. This occurs regardless of mode.

4) Emergency Heat Override – Switch 7

In the unlikely event of a compressor failure a heat pump unit
may be switched to operate in only the electric heat mode until
repairs can be made. Moving Dip Switch 7 to ‘ON’.

Note: PTAC must be disconnected from power supply
when making any confi guration changes.

Temperature

Range

Dip

Switch

Low

High

3

4

60

90

On

On

63

90

On

Off

66

90

Off

Off

69

90

Off

On

Cooling Range Switches 3 & 4

Heating Range Switches 1 & 2

Temperature

Range

Dip

Switch

Low

High

1

2

60

90

On

On

60

87

Off

On

60

84

Off

Off

60

81

On

Off

Figure 11

Factory Dip Switch Confi guration

1 2 3 4 5 6 7 8

O

N