beautypg.com

Extension installation, Wall sleeve extension sealant locations – Friedrich HEAT PUMPS User Manual

Page 11

background image

11

920-087-04

If the wall is thicker than allowed in the notes in Figure 6, a sheet
met al wall sleeve ex ten sion and fl ashing MUST be used.

Installation Instructions for the PXWE – 4" Wall
Sleeve Extension

The following points MUST be considered when installing a wall
sleeve extension:

1 Provision must be made to direct excess condensate from

the back of the wall sleeve into the extension then outside
the building or to a drainage system.

2. Air baffl es must be mounted to properly direct air fl ow to

and from the condenser.

3. The wall sleeve extension design must allow for the prop er

mount ing of the grille.

4. Caulking is required at all sites where condensate or

ex ter nal water could potentially infi ltrate into the building.

5. Fabricate and install metal fl ashing in wall to serve as a drip

panel. Refer to drawing for more information.

6. Condensate notches and overfl ow slots must be kept clear

of sealant and gaskets so con den sate can fl ow freely into
the wall sleeve extension.

NOTE: Improper fabrication or installation of a wall sleeve
extension will impair PTAC performance.

Extension Installation

Secure the wall sleeve extension to the wall sleeve before
installing it in the wall. Refer to Figure 8 for a guide for fabrication
of a condensate drip panel. The panel MUST extend the full depth
of the wall sleeve and the wall sleeve extension.

Pay particular care in seal ing and caulking the panel where it
makes contact with the wall sleeve (see Figure 8). After installation
in the wall, secure with fasteners through the sides. Use a good
grade of silicone sealant around the sleeve extension. Seal all
exposed screw heads. When the installation is complete, the
outside grille should be attached to the wall sleeve extension.

Section II — Deep Wall Installation (PXWE)

Figure 8

IMPORTANT NOTE: The silicone bead MUST extend 3"
up the side of the two fl anges to pre vent condensate
from leaking.

Wall Sleeve Extension, 42" X 16" Frame, 20 gauge min i mum, painted or alu min i um

Outside Edge

Insulation

Wall Sleeve

Air Baffl es

Condensate
Notches (4)

Condensate

Drip Panel

(Field

Supplied)

Sealant inside (4) bottom corners

Drip
Edge

Width of Wall

PXWE Wall Sleeve
Extension

Wall Sleeve Extension Sealant Locations