beautypg.com

Refrigeration system – Follett HCE1000W User Manual

Page 23

background image

23

High pressure vapor

high side
refrigeration
line run

filter
dryer

thermostatic
expansion
valve

high side
service port

low side
service port

condenser

heat exchanger

low side
refrigeration
line run

compressor

High pressure liquid

Low pressure liquid

Low pressure vapor

Refrigeration system diagram

Air

temperature

Air-cooled condensers

60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C 100˚F/38˚C

Pressure (psig)
discharge/suction

218/31 241/33 277/35 313/38 349/41

1503/213kPa

1661/234kPa

1909/241Kpa

2158/262kPa

2406/282kPa

15.03/2.13bar

16.61/2.34bar

19.58/2.41bar

21.58/2.62bar

24.06/2.82bar

Water

temperature

Water-cooled condensers

60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C 100˚F/38˚C

Pressure (psig)
discharge/suction

279/33 225/33 231/33 232/34 236/40

1923/227kPa

1551/234kPa

1592/227kPa

1599/234kPa

1627/275kPa

18.96/2.27bar

15.51/2.34bar

15.92/2.27bar

15.99/2.34bar

16.27/2.75bar

Note:

The water control valve is factory set to maintain 275 ± 15 psi discharge pressure @ 70˚F water.

Refrigeration system