Profibus settings, Server side connection parameters – FieldServer Profibus FS-8700-113 User Manual
Page 6
![background image](/manuals/103802/6/background.png)
FS-8700-113 Profibus DP Slave Driver Manual
Page 6 of 13
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
CONFIGURING THE FIELDSERVER AS A PROFIBUS DP SERVER
5
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Profibus DP Master.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Profibus communications, the driver independent FieldServer buffers need to be declared in
the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section,
and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section.
Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1
Profibus Settings
Section Title
Bridge
Column Title
Function
Legal Values
System_Station_Address* Profibus Station Address of the FieldServer 1-125
Example
// Bridge
Bridge
Title
, System_Station_Address
Profibus DP , 5
The Profibus Station Address can also be set via the two rotary switches on the side of the FieldServer in which
case the System_Station_Address setting must be omitted from the configuration file. The settings specified in the
configuration file will override the settings on these switches.
5.2
Server Side Connection Parameters
5
Section Title
Connections
Column Title Function
Legal Values
Adapter
Adapter Name Prof_DP_MS
Example
// Server Side Connections
Connections
Adapter
Prof_DP_MS
5
The X30 Profibus card auto-senses the Baud rate