Appendix B. Troubleshooting

Appendix B.1. Continuous Map Descriptors

The Driver is not able to split data between 2 Data Arrays when writing, or to read a Server mapping that is
discontinuous.

For example, on the Server Side:
If:
Server map 1: N21: 0-31
Server map 2: N21: 32-100

This will panic the FieldServer and crash RS view as the DH+ will attempt to map N21: 0-100. If set up as Server
Map 1: N21: 0-100, no problems are experienced.

Appendix B.2. Reading B File Types

It is advisable to read all data from one B type file into the same data array in one contiguous read if possible.
Doing otherwise may result in problems when reading these points.

Appendix B.3. Checksum

When selecting checksum options for DH+ devices communicating to the FieldServer, take note that BCC (Block
Check Sum) is supported, whereas CRC (Cyclic Redundancy Check) is not.

Appendix B.4. DH+ as FieldServer Server

If the FieldServer is to be polled by the DH+ network, then it is important to declare the station address in the
“FieldServer” portion of the configuration file. Refer to Section 6.1. This sets the FieldServer address to 11. The
Node_ID on the Server side must then be the same as the station address declared.