beautypg.com

Iv: understanding the indicator lights – Firex FADCQ User Manual

Page 16

background image

IV: UNDERSTANDING THE INDICATOR LIGHTS

The Model FADCQ features 3 lights with 5 distinct colors. Use the chart below to determine what the
different indicator light colors and flashes mean:

• Constant GREEN on

- AC power is present.

• GREEN is off

- AC power is NOT present. Unit may be operating on

battery back-up or battery only power.

• RED and BLUE blink once a minute

- Unit is functioning properly and is checking for hazardous smoke

and CO levels, periodically checking the battery, and monitoring the
interconnect for signals from other smoke, heat, and CO alarms.

• BLUE flashes four times immediately

-CO alarm senses dangerous levels of CO and sounds the alarm.

after four horn alarms

• RED-YELLOW-ORANGE blink

- Smoke alarm senses smoke and sounds an alarm.

between horn alarms

• RED blinks once every ten seconds

- Smoke alarm is in Quick Quiet

TM

False Alarm Control

TM

mode and is

quieting an unwanted alarm.

• BLUE blinks once every ten seconds

- The CO alarm has been reset. After approximately six minutes of

silence the CO alarm will check for the presence of CO gas. If it is
above 70 ppm, the unit will begin to sound the CO alarm again; if the
level is below 70 ppm the unit remain quiet.

• RED-YELLOW-ORANGE AND BLUE

- (Interconnected alarms only) another smoke or CO alarm has

are off and detector horn is sounding

sensed smoke or CO and is signaling an alarm.

• RED blinks 3 times every ten seconds

- Latching indicator. This unit initiated and memorized a smoke alarm

condition. NOTE – if GREEN is not illuminated, there is no AC
power for the alarm. The RED will blink 3 times and repeat once per
minute. Press Test Button to reset.

• BLUE blinks 4 times every ten seconds

- Latching indicator. This unit initiated and memorized a CO alarm

condition. NOTE – if GREEN is not illuminated, there is no AC
power for the alarm. The BLUE will blink 4 times and repeat once
per minute. Press Test Button to reset.

• YELLOW blinks 5 times every minute

- Battery Warning. Indicates weak or improperly connected battery,

preceded by an audible beep. Press the Test Button to silence the
beeping for approximately 8 hours. Replace battery as soon as
possible.

• YELLOW blinks 7 times every minute

- Low Battery Warning. Indicates very weak or improperly connected

battery, preceded by an audible beep. The battery must be
replaced immediately for your protection. Smart Quiet (quiets low
battery warning) is inoperable.

16