FS-8700-39 EST3 Driver Manual

Page 24 of 26

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix C.1.2. Output data format

Each output device is associated with a 16-bit value. This value consists of two byte fields, the command (LSB) and the
attribute (MSB).

FieldServer Data Array Object (16-bit)
Attribute (8-bit)

Command (8-bit)


These values are provided by the EST panel and are described in the EST3 ECP protocol specification as follows. These values
will be put in the Command field.

Command

Encode Value

Activate / Away

01h

Enable

02h

Restore / Disarm 11h
Disable

12h


The attribute byte must be set for writes to Relay, LED outputs and DeviceTest

For Relays, the attribute values are:

Attribute (Relay) Encode Value
Enable

2h

Activate

101h

Restore

11h

Disable

12h


For LED’s, the attribute values are:

Attribute (LED) Encode Value
On

101h

Slow Flash

201h

Fast Flash

301h

Disable

12h

Enable

2h

Off

1h

For DeviceTest (Signature Devices Only), the attribute values are:

Attribute (DeviceTest)

Encode Value

TestActive1
Places the device in its primary active state (Alarm, Monitor, Supervisory, SecurityAlarm, etc.

201h

TestTrouble
Places the device in CommonTrouble

301h

TestActive2
Places Security devices capable of tamper, in SecurityTamper.
Places sensors capable of PreAlarm in Prealarm

401h