8.2 Example OPC Server Setup

Remote Data
Array

The Data Array set up on the FieldServer

Start Address

Offset into the Data Array where the data will be stored. The default of 0 is applicable in
most cases.

Length in items

Set to the number of elements in the FieldServer Data Array or less. The maximum length is
determined by the datatype of the Data Array as follows:

Float and UInt32 – 325
UInt16 – 650
Byte – 1300
Bit - 2600

Store data as

Datatype for the stored data. Per the OPC standards, Float is the suggested data type

Polling Setup

The rate at which the OPC Server polls the FieldServer.

Primary Rate

The rate at which the OPC Server will poll the FieldServer

Secondary Rate

The rate at which the OPC Server will poll the FieldServer after the access time is expired. If
the access time is less than the primary poll rate, the secondary rate will be used.

Phase

Time delay before initial poll takes place

Access Time

Used internally to set the data access expiration time. The FieldServer will be polled at the
primary rate until this time expires, after which it will be polled at the secondary rate.