EXAMPLE SETUP
8.1 Sample FieldServer Setup
In this example, the low level driver (Modbus) is irrelevant to the operation of the OPC Server, however the user needs to be aware of how field addresses map to Data
Array addresses.
FieldServer
Title
DAA_TEST
// Client Side Connections
Connections
Port
, Baud
, Parity
, Data_Bits
, Stop_Bits
, Protocol
P1
, 9600
, None
, 8
, 1
, Modbus_RTU
// Server Side Connections
connections
adapter
, protocol
n1
, SMT
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
SDA_BUA900_40001
, Float
, 200
Nodes
Node_Name
, Node_ID
, Protocol
, Retries
, Port
BUA900
, 31
, Modbus_RTU
, 8
, R1
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function , Node_Name , Address
, Length , Scan_Interval
CMD_AI_BUA900_1
, SDA_BUA900_40001 , 00
, RDBC
, BUA900
, 40001
, 100
, 5s
CMD_AI_BUA900_2
, SDA_BUA900_40001 , 100
, RDBC
, BUA900
, 40101
, 100
, 5s