beautypg.com

Example setup, Sample fieldserver setup – FieldServer FS-8707-06 User Manual

Page 10

background image

FS-8707-06 FST OPC Server for FieldServer

Page 10 of 15

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

8

EXAMPLE SETUP

8.1 Sample FieldServer Setup

In this example, the low level driver (Modbus) is irrelevant to the operation of the OPC Server, however the user needs to be aware of how field addresses map to Data
Array addresses.

FieldServer

Title

DAA_TEST

// Client Side Connections

Connections

Port

, Baud

, Parity

, Data_Bits

, Stop_Bits

, Protocol

P1

, 9600

, None

, 8

, 1

, Modbus_RTU

// Server Side Connections
connections

adapter

, protocol

n1

, SMT

Data_Arrays

Data_Array_Name

, Data_Format

, Data_Array_Length

SDA_BUA900_40001

, Float

, 200

Nodes

Node_Name

, Node_ID

, Protocol

, Retries

, Port

BUA900

, 31

, Modbus_RTU

, 8

, R1

Map_Descriptors

Map_Descriptor_Name

, Data_Array_Name

, Data_Array_Offset

, Function , Node_Name , Address

, Length , Scan_Interval

CMD_AI_BUA900_1

, SDA_BUA900_40001 , 00

, RDBC

, BUA900

, 40001

, 100

, 5s

CMD_AI_BUA900_2

, SDA_BUA900_40001 , 100

, RDBC

, BUA900

, 40101

, 100

, 5s