Installation procedure, Trouble display, Electric wiring – haier AU282AHERA User Manual

Page 24

background image

22

Electric wiring

(1) Before starting test run (for all Heat pump models)

Confirm whether the power source breaker (main switch) of the unit has been
turned on for over 12 hrs to energize the crankcase heater in advance of operation.

(2) Test run

Run the unit continuously for about 30 minutes, and check the following.

Suction pressure at check joint of service valve for gas pipe.
Discharge pressure at check joint on the compressor discharge pipe.
Temperature difference between return air and supply air for indoor unit.

Installation Procedure

Note:
For display of LED board, the number "1" mean the LED is light. the number "0" mean
the LED is OFF.
User should not to change the dip switch of LED board.
Please consult the operation and instrucion to get detailed information about outdoor
unit trouble.

Trouble description

Abnormal of DC moter

Compressor discharging temprerture protection

Spdu module over current protection

Abnormal of piping sensor or suction sensor

High pressure protection

Eeprom failure

Communication error between indoor and outdoor
unit

Abnormal of outdoor ambietn sensor

Compressor JAM

Abnormal of compressor discharge sensor

Compressor vibration abnormal

The power supply is not the 50Hz

Display of LED borad

Analyze and diagnose

Spdu module failure

00001

Spdu module failure

00010

00011

00100

00101

00110

Compressor start-up abnormal

Rotor of inner compressor is malposition

Position-inspect circuit failure

Compressor failure

Compressor suction sensor over high

Communication error between main board and
spdu module

Low pressure protection

00111

01000

01001

01110

01111

10000

10001

10010

10011

10100

10101

10110

11000

01010

Jam of DC motor or motor failure

Communication fail over 4min

Compressor discharging tempreature
over 120 centigrade

Current of spdu module over 21A last
4set
Outdoor ambietn sensor short-circuit or
open-circuit last 3sec

Piping sensor or suction sensor short-
circuit or open-circuit last 3sec

System high pressure over 4.5Mpa

Compressor discharge sensor short-
circuit or open-circuit

The power supply is not the 50Hz

Outdoor main board eeprom fail

Inner compressor is

abnormal

Compressor vibration abnormal when
start-up
Compressor start-up abnormal

Rotor of inner compressor is malposition
when start-up
Position-inspect circuit failure of spdu
module

Compressor failure

In operation the suction temperature
over 40 centigrade
Communication error between main
board and spdu module

System low pressure

under

0.15Mpa

Spdu module temperture protection

10111

Spdu module temperture is too high

10. Trouble display

LED 5-4-3-2-1