(2) Piping size

(3) Limitations for one way piping length and vertical height difference.

Precautions for refrigerant piping

Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check flare-connected area for gas leakage.

Connecting method (indoor unit)
Apply refrigerant oil at half union as large and flare nut.
To bend a pipe, give the roundness as possible not to crush
the pipe.
When connecting pipe, hold the pipe centre to centre then
screw nut on by hand, refer to Fig.
Be careful not to let foreign matters, such as sands enter
the pipe.

(4) Piping connection

Forced fastening without centering
may damage the threads and cause a
gas leakage.

Pipe diameter

Fastening torque

Liquid pipe 6.35mm

Gas pipe 15.88mm

Liquid pipe 9.52mm

Gas pipe 19.05mm

14.2-17.2N.m

61.8-75.4N.m

32.7-39.9N.m

97.2-118.6N.m

Gas pipe 12.7mm

49.5-60.3N.m

Install the removed flare nuts to
the pipes to be connected, then
flare the pipes.

M o d e l

One way piping length

Vertical height difference
(between indoor and outdoor)

less than 20 m

AU362AHERA AU36NAHERA
AU422AIERA AU42NAIERA
AU522AIERA AU52NAIERA

AU122AEERA

AU182AFERA
AU242AGERA AU282AHERA

Gas pipe

15.88x1.0mm

Liquid pipe

Gas pipe

9.52x0.8mm

19.05x1.0mm

Liquid pipe

9.52x0.8mm

Gas pipe

12.7x1.0mm

Liquid pipe

6.35x0.8mm

Refrigerant piping

17

Installation Procedure

90+0.5

AU422AIERA
AU42NAIERA
AU522AIERA
AU52NAIERA

AU242AGERA
AU282AHERA
AU362AHERA
AU36NAHERA

AU122AEERA
AU182AFERA

less than 30 m

less than 15 m

less than 15 m

less than 50 m

less than 30 m